| Conductor Size AWG | Temperature ℃ | Conductor No./mm | No. of Core | Insulation Thickness (mm) | Jacket Thickness (mm) | OD (±0.1mm) | 
			
				| 8 |  | 65/0.405 |  | 1.14 |  | 6.15 | 
			
				| 10 |  | 41/0.405 |  | 0.76 |  | 4.62 | 
			
				| 12 |  | 65/0.254 |  | 0.76 |  | 3.99 | 
			
				| 14 |  | 41/0.254 |  | 0.76 |  | 3.5 | 
			
				| 2 |  | 32/1.121 |  | 1.14 | 0.76 | 11.22 | 
			
				| 4 |  | 165/0.405 |  | 1.14 | 0.76 | 9.91 | 
		
	
 
	 
	 
	
		
			
			
			
		
		
			
				| Conductor Size AWG | Temperature ℃ | Conductor No./mm | No. of Core | Insulation Thickness (mm) | Jacket Thickness (mm) | OD (±0.1mm) | 
			
				| 6 |  | 105/0.405 |  | 1.14 | 0.76 | 8.69 | 
			
				| 8 |  | 65/0.405 |  | 1.14 | 0.76 | 7.67 | 
			
				| 10 |  | 41/0.405 |  | 0.76 | 0.38 | 5.28 | 
			
				| 12 |  | 65/0.254 |  | 0.76 | 0.38 | 4.75 | 
			
				| 14 |  | 41/0.254 |  | 0.76 | 0.38 | 4.26 | 
		
	
 
	 
	Size range is limited to: 14AWG-2000 kcmil for types TW, THW and THW-2; 14AWG-1000 kcmil for Type THHW.
	
	Standard: Thermoplastic-Insulated Wires and Cables UL83.
	Rated voltage: 600V.
	Maximum temperature: Type TW 60℃ dry or wet; Type THW dry or wet; Type THW-2
	90℃ dry or wet; Type THHW 90℃ dry 75 ℃ wet.
	Conductor: Soft-annealed copper, aluminum or copper aluminum.
	Insulation: PVC
	Passed UL VW-1 & FT2 vertical flame test.
	75 ℃ oil resistant. Gasoline resistant, Suitable for use in wet or dry
	locations. Building wire for use in commercial and industrial's within well
	casing for wiring submersible pump units.